Phase |
3-Phase input / 3-Phase
Output (*1 phase input / 3 phase output available to 60KVA) |
Model Size |
10KVA |
20KVA |
30KVA |
40KVA |
50KVA |
60KVA |
80KVA |
100KVA |
120KVA |
160KVA |
200KVA |
240KVA |
300KVA |
320KVA |
INPUT |
INPUT VOLTAGE (Specify) |
208VY / 380VY / 400VY /
415VY or 220V / 380V / 460V |
INPUT RANGE |
All above are nominal input
voltages, and can vary ±20% |
INPUT FREQUENCY |
50 / 60 Hz ±7% |
POWER WALK IN |
0% - 100% : 20 SECONDS |
OUTPUT |
OUTPUT VOLTAGE (Specify) |
208VY / 380VY / 400VY
/ 415VY or 220V / 380V / 460V |
For 50hz output, we recommend 230/400V
wye 4 wire (Adjustable ±10%), the common market standard,
to duplicate both the continental 220/380V 4 wire standard,
and the British 240/415V 4 wire standard. |
All above are nominal output voltages,
and adjustable by potentiometer by ±10% |
VOLTAGE REGULATION |
±1% of settings |
WAVEFORM |
SINEWAVE |
OUTPUT POWER FACTOR |
0.8 |
OUTPUT FREQUENCY (Specify) |
50 or 60 Hz ± 0.05
Hz |
PHASE SHIFT UNDER 100%
UNBALANCE LOAD |
<0.5º |
THD (LINEAR LOAD) |
<2% |
OVERLOAD |
<100% |
CONTINUOUS |
110-125% |
15 MINUTES |
125-150% |
10 MINUTES |
>150% |
1 MINUTE |
OVERALL
CHARACTERISTICS |
Model Size |
10KVA |
20KVA |
30KVA |
40KVA |
50KVA |
60KVA |
80KVA |
100KVA |
120KVA |
160KVA |
200KVA |
240KVA |
300KVA |
320KVA |
OVERAL EFFICIENCY |
90% |
91% |
91% |
91.5% |
92% |
92% |
92.5% |
93% |
93% |
93% |
93% |
95% |
95% |
95% |
MAXIMUM HEAT
DISSIPATION (KW) |
1.1 |
1.3 |
1.9 |
2.6 |
3 |
3.5 |
4.6 |
5.4 |
6.5 |
8.7 |
8.7 |
6.5 |
6.5 |
6.5 |
DIMENSIONS (H x W x D) mm / in |
1450 x 550 x 1000
58 x 22 x 40 |
1600 X 1100 X 1000
63 x 43 x 40 |
1600 X 2200 X 1000
63 X 86 X 40 |
WGT. KG/lbs |
270 / 595 |
300 / 663 |
400 / 884 |
480 / 1060 |
550 / 1215 |
680 / 1502 |
820 / 1807 |
950 / 2094 |
1180 / 2601 |
1450 / 3196 |
2500 / 5512 |
2700 / 5952 |
3000 / 6614 |
3100 / 6834 |