Model |
4KSS 6050/5060 |
Capacity |
4KVA/3.2KW |
Input |
Voltage |
120 or 220V-15%/+20% |
Voltage Range |
-15%/+20% |
Current
Requirement |
220V - 20.9A @ Full Load (31.4A @ Current limit) |
120V - 38.3A @ Full Load (57.5A @ Current limit) |
Frequency |
Any Frequency from 45 65 hz (specify if 400hz) |
Phase |
Single |
Output |
Voltage |
120 or 220Vac ±20% Adjustable from nominal |
Voltage Regulation |
±1% From setpoint |
Frequency |
50Hz or 60Hz (Switch selectable) (400Hz
available) |
Frequency Regulation |
±0.0005Hz |
Harmonic Distortion |
< 3% at 100% Linear Load |
Output Waveform |
Pure Sinewave |
Output Current @ .8pf |
220V - 18.1A |
120V - 33.3A |
Overload@150% for 30 seconds |
220V - 27.2A |
120V - 50A |
Efficiency |
|
AC to AC |
>85% |
|
|
Power Factor |
0.8 |
Crest Factor |
3:1 |
Indicator-Detachable & Remote
Control |
LCD |
Automatically configures to monitor voltage,
frequency, and loading, simultaneously. |
LED |
Line: Green LED |
Inverter: Green LED |
Fault: Red LED |
Overload: Yellow LED |
|
Audible Alarm |
|
Overload |
Continuously beeping |
Fault |
Continuously beeping |
Protection |
|
Overload |
150% Delay 30 seconds, current limited |
Short Circuit |
Current limited and cut-off, fuse and breaker |
EMI Filter |
10-100KHz at 40dB; 100KHz-100MHz at 70dB |
Over Temperature |
Inverter auto cut-off when heat sink temp. over
80 ° C |
Dimension |
|
Depth |
22.9in/58.2cm |
Width |
9.63in/24.5cm |
Height |
27.75in/70.5cm |
Environment |
|
Operation Temperature |
0-40° C; 32-104° F |
Relative Humidity |
20-90% (non-condensing) |
Noise Level |
< 58dB (at 1 meter) |
Weight |
|
LBS/KG |
232lbs/105.5kg on wheels |